Weil-McLain · Boiler troubleshooting

Combustion air and boiler room ventilation

ECO Tec Series 3

What is going on

Direct vent is the normal approach; direct exhaust is possible with the approved kit. Air openings depend on the room and other appliances.

Check in this order

  1. For a boiler alone in the room, no ventilation openings are needed if direct vent is used and the service clearances are met.
  2. If the room does not provide the minimum service clearances, provide two openings sized at 1 square inch free area per 1,000 Btuh of boiler input.
  3. If other gas or oil appliances share the space, size the openings per Figure 33 on page 31.
  4. Reinstall the jacket door after servicing so it is securely fastened and the boiler cannot draw room air from inside the boiler room.

Applies to: Boiler room air supply

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 11. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.