External blocking via DIS input

Vitocrossal 200 CI2

What is going on

A closed contact at DIS shuts the burners down in a controlled way. Choose the combustion air device option that matches the installation.

Check in this order

  1. If no combustion air device is connected, keep the factory jumper.
  2. For a dry contact combustion air device feedback, wire it to DIS.
  3. For a 24VAC combustion air device with dry contact feedback, wire it to DIS.
  4. If high starting currents occur, add a contactor between the contact and the load.

Applies to: DIS digital input at MZIO

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 Installation Instructions, p. 25. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.