Weil-McLain · Boiler troubleshooting
Contaminant sources to avoid for combustion air
What is going on
Combustion air must not contain chemicals or dust that can corrode the burner or heat exchanger. Keep air intakes and boiler room air away from these products and areas.
Likely causes
- Chlorine or halogen compounds from sprays, bleaches, pool chemicals, cleaners and refrigerant leaks
- Acid, solvent, glue and paint vapors
- Excessive dust and dirt from construction or remodeling
Check in this order
- Keep chloro/fluorocarbon spray cans, permanent wave solutions, chlorinated waxes, pool chemicals, calcium chloride, sodium chloride (softener) and refrigerant leaks away from the air source.
- Keep paint and varnish removers, muriatic acid, cements, glues and building adhesives away from the air source.
- Keep antistatic dryer softeners and chlorine-type laundry bleaches and solvents away from the air source.
- Avoid intake locations near dry cleaning, swimming pools, metal fabrication, beauty shops, refrigeration repair, photo processing, auto body, plastic manufacturing, furniture refinishing, new construction, remodeling and garages with workshops.
- For direct vent, do not terminate air piping where it can pull in contaminated air.
Applies to: Combustion air intake and boiler room air
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF Series 1 Boiler Manual, p. 26. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.