Viessmann · Boiler troubleshooting
Check flue side for leaks
What is going on
Check the flue gas collector, boiler body and gaskets for leaks. Use a dew point hygrometer at full load. Condensed water on the outside of the flue gas collector or thermal insulation also indicates a leak. Detach thermal insulation parts if needed.
Likely causes
- Failed flue gas collector gasket or boiler body seal
Check in this order
- Run the boiler at full load.
- Check the flue gas collector and boiler body for leakage with a dew point hygrometer.
- Look for condensed water on the outside of the flue gas collector or on insulation.
- Check the burner door gasket for correct seating.
- After the burner is removed, finish with a CO2 test per the page 26 points and record the values in the report on page 95.
Applies to: Vitocrossal 200 CI2 boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 Service Instructions, p. 33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.