System Layout 2: radiator circuit with low-loss header and DHW

Vitodens 200-W

What is going on

Vitodens 200-W B2HB with one heating circuit and a low-loss header, plus DHW. Used when heating circuit flow is above the boiler maximum water flow.

Check in this order

  1. Install a low-loss header; it is strongly recommended if flow exceeds page 31 values or is unknown.
  2. Install the boiler pump 20 and heating circuit pump 28/20 (coding address 53).
  3. Fit the Viessmann temperature sensor for the low-loss header.
  4. Note the expansion tank location as shown.
  5. Pipe the DHW circulating pump F into the boiler.

Applies to: Vitodens 200-W B2HB

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Installation Instructions, p. 34. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.