Viessmann · Boiler troubleshooting

Preventing oxygen-related corrosion in heating water

Vitocrossal 200 CI2

What is going on

Oxygen in the heating water causes corrosion of ferrous parts. Keep the system pressure above atmospheric at every point, including the pump suction side.

Likely causes

  • Open vented expansion vessels
  • Negative pressure on the pump suction side
  • Gas-permeable components such as some plastic underfloor pipes

Check in this order

  1. Check that the system pressure stays above atmospheric pressure at every point.
  2. Check the expansion vessel precharge pressure at least during the annual service.
  3. Separate permeable plastic pipe circuits from the boiler circuit with a corrosion-resistant heat exchanger.
  4. Where oxygen ingress is likely, add oxygen binder (sodium sulphite) at 5 to 10 ppm (5 to 10 mg/L).
  5. Keep the heating water pH between 8.2 and 9.5.
  6. Get a certificate of suitability for any chemical additive from its manufacturer.

Applies to: Closed heating water systems

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 service instructions, p. 95. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.