Weil-McLain · Boiler troubleshooting
Add antifreeze to the system
What is going on
Use only antifreeze listed by WM Technologies for ECO Tec boilers.
Check in this order
- Determine the freezing temperature needed for the lowest likely water temperature.
- Find the antifreeze concentration by volume for that temperature from the manufacturer's data.
- Add up the total water volume of system piping and components, including the expansion tank and boiler.
- Multiply the total volume by the antifreeze percent to get gallons of antifreeze.
- Do not exceed 50% antifreeze by volume.
- Flush any system that used glycol before installing the boiler.
Applies to: ECO Tec Series 3 80/110/150/199
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 130. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.