Weil-McLain · Boiler troubleshooting

Add antifreeze to the system

ECO Tec Series 3

What is going on

Use only antifreeze listed by WM Technologies for ECO Tec boilers.

Check in this order

  1. Determine the freezing temperature needed for the lowest likely water temperature.
  2. Find the antifreeze concentration by volume for that temperature from the manufacturer's data.
  3. Add up the total water volume of system piping and components, including the expansion tank and boiler.
  4. Multiply the total volume by the antifreeze percent to get gallons of antifreeze.
  5. Do not exceed 50% antifreeze by volume.
  6. Flush any system that used glycol before installing the boiler.

Applies to: ECO Tec Series 3 80/110/150/199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 130. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.