Connect the 120VAC gateway to the boiler control

Versatronik 505 & 505D

What is going on

The gateway is wired to the control's LON card with the supplied CAT-5 cable and to the BACnet IP network by RJ45. The control's LON card must be installed. Refer to the manual for the specific boiler control.

Check in this order

  1. Confirm the control has its LON communication card installed.
  2. Plug one end of the supplied 3 ft (91 cm) CAT-5 cable into the RJ45 socket on the control's LON card.
  3. Plug the other end into the RJ45 socket inside the Versatronik 505 gateway.
  4. Plug the BACnet IP RJ45 cable into the gateway.
  5. Plug the 120VAC power cord into the gateway.

Applies to: Versatronik 505 with Vitotronic 100 GC1/GC1B, 300 GW2 or 300 GW5B

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 505 & 505D BACnet IP gateway manual, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.