Weil-McLain · Boiler troubleshooting

Convert propane boiler to natural gas

ECO Tec Series 3

What is going on

Same process as the propane conversion, using the natural gas kit and with the propane orifice removed. Natural gas boilers have no orifice.

Check in this order

  1. Follow the propane conversion steps using the correct natural gas kit.
  2. Remove the propane gas orifice from between the gas pipe and the venturi.
  3. Set the boiler control fuel type to Natural Gas if propane was selected.
  4. Turn the throttle screw fully clockwise until it stops, then turn it counterclockwise the number of turns in the setting table.
  5. Set the control and run the full startup with a combustion analyzer.

Applies to: ECO Tec 80/110/150/199 propane to natural gas

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 Boiler Manual, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.