Viessmann · Boiler troubleshooting
Integrating control unit into LON
What is going on
The LON communication module is factory installed on the Vitocrossal 300 control unit. The Vitotronic 200-H needs the LON module accessory. Cascade combinations cannot exceed 8 boiler sections.
Check in this order
- Remove the terminal end resistor on A to continue the LON connection.
- For Vitotronic 200-H, plug in the LON communication module accessory.
- Give each participant a unique participant number within the LON.
- Set the same system number (coding 98, General group) on all boilers in a multi-boiler system.
- Encode only one control unit as fault manager.
- Allow up to several minutes for LON data transfer to start.
- Use Vitotronic 300 GW6C for CA3B Dual Fuel 2.5 to 4.0, and GW6C for 5.0 and 6.0.
Applies to: Vitocrossal 300 CA3B Dual Fuel LON network
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 installation instructions, p. 35. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.