Connect compiled failure alarm (CM2)

Vitotronic 300

What is going on

Wire a 120 VAC visual and/or audible alarm to the CM2 boiler's compiled failure output.

Check in this order

  1. Disconnect power to the control and the burner.
  2. Connect the alarm device (120 VAC, 60 Hz, max. 2 FLA, AWG 14 wire) to the terminal strip in the boiler control connection enclosure as shown in the diagram.

Applies to: CM2 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW2 installation and service instructions, p. 37. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.