Weil-McLain · Boiler troubleshooting
Check ignition cable and ground wiring
What is going on
Verify ignition cable resistance and ground continuity.
Likely causes
- Ignition cable out of range
- Poor ground connection
Check in this order
- Measure ignition cable resistance. A good cable reads between 950 and 1050 ohms. Replace if outside this range.
- Inspect the ground wire from the heat exchanger access cover to the ground terminal screw.
- Check ground continuity with a continuity meter.
- Replace the ground wires if results are not satisfactory.
- Verify all wiring is in good condition and securely attached.
Applies to: ECO Tec Series 3 gas boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 142. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.