Check ignition cable and ground wiring

ECO Tec Series 3

What is going on

Verify ignition cable resistance and ground continuity.

Likely causes

  • Ignition cable out of range
  • Poor ground connection

Check in this order

  1. Measure ignition cable resistance. A good cable reads between 950 and 1050 ohms. Replace if outside this range.
  2. Inspect the ground wire from the heat exchanger access cover to the ground terminal screw.
  3. Check ground continuity with a continuity meter.
  4. Replace the ground wires if results are not satisfactory.
  5. Verify all wiring is in good condition and securely attached.

Applies to: ECO Tec Series 3 gas boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 boiler manual, p. 142. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.