Weil-McLain · Boiler troubleshooting

Check control module and expansion module fuses

SlimFit Series 2

What is going on

Check fuses before replacing the control module or major components such as the blower. A blown fuse can stop the control or other components.

Likely causes

  • Blown low voltage control fuse
  • Blown line voltage control fuse
  • Blown expansion module fuse

Check in this order

  1. Turn OFF power to the boiler at the external line switch.
  2. Remove the jacket top panel to expose the control module and expansion module.
  3. Remove and inspect the two control fuses and the expansion module fuse.
  4. If replacing a fuse low voltage fuse (item 1) is a 3 amp fast-blow, Littelfuse 0287003. Line voltage fuse (item 2) is a 12 amp fast-blow, Littelfuse 0314012 MXP or Bussman ABC-12-R.
  5. Never jumper a fuse or use any fuse other than the specified type.
  6. Reinstall the jacket top panel and jacket door.
  7. Restore power at the external line switch and verify operation.

Applies to: SlimFit 1000-2000 MBH Series 2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 94. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.