Check control module and expansion module fuses
What is going on
Check fuses before replacing the control module or major components such as the blower. A blown fuse can stop the control or other components.
Likely causes
- Blown low voltage control fuse
- Blown line voltage control fuse
- Blown expansion module fuse
Check in this order
- Turn OFF power to the boiler at the external line switch.
- Remove the jacket top panel to expose the control module and expansion module.
- Remove and inspect the two control fuses and the expansion module fuse.
- If replacing a fuse low voltage fuse (item 1) is a 3 amp fast-blow, Littelfuse 0287003. Line voltage fuse (item 2) is a 12 amp fast-blow, Littelfuse 0314012 MXP or Bussman ABC-12-R.
- Never jumper a fuse or use any fuse other than the specified type.
- Reinstall the jacket top panel and jacket door.
- Restore power at the external line switch and verify operation.
Applies to: SlimFit 1000-2000 MBH Series 2
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 94. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.