Viessmann · Boiler troubleshooting

External blocking via switching contact

Vitotronic 300 GW6B

What is going on

Blocks the boiler or cascade from an external floating contact. Connection is on plug aVD.2/aVD.3, or on the EA1 extension for cascade control units.

Check in this order

  1. Use a potential-free contact only.
  2. Single boiler when the contact closes, the boiler shuts down.
  3. Multi boiler when the contact closes, the burners are shut down in a controlled way on each boiler, and any connected circuit or system pump stops. Shut-off devices close.
  4. The heating system has no frost protection while blocked.
  5. On plug aVD set coding 99 in the General group to decide what the input influences. Never change coding 99:0 in a cascade control unit.
  6. On EA1 extension set 5d (DE1), 5e (DE2) or 5f (DE3) in the General group to 3 or 4.
  7. In cascade control units, make the connection on the EA1 extension.

Applies to: Single boiler and cascade control units

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW6B installation and service manual, p. 41. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.