Viessmann · Boiler troubleshooting
External blocking via switching contact
What is going on
Blocks the boiler or cascade from an external floating contact. Connection is on plug aVD.2/aVD.3, or on the EA1 extension for cascade control units.
Check in this order
- Use a potential-free contact only.
- Single boiler when the contact closes, the boiler shuts down.
- Multi boiler when the contact closes, the burners are shut down in a controlled way on each boiler, and any connected circuit or system pump stops. Shut-off devices close.
- The heating system has no frost protection while blocked.
- On plug aVD set coding 99 in the General group to decide what the input influences. Never change coding 99:0 in a cascade control unit.
- On EA1 extension set 5d (DE1), 5e (DE2) or 5f (DE3) in the General group to 3 or 4.
- In cascade control units, make the connection on the EA1 extension.
Applies to: Single boiler and cascade control units
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 GW6B installation and service manual, p. 41. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.