Navien · Boiler troubleshooting
Common vent system overview (up to 7 NPE water heaters)
What is going on
One NCB700 and up to 7 NPE water heaters can share one common vent, using shared intake and exhaust pipes. This is a Category IV appliance that runs with positive pressure in the vent. Improper venting can cause carbon monoxide poisoning. Only licensed professionals should install the vent, and it must follow ANSI Z223.1/NFPA 54 or CAN/CGA B149.1 plus local codes.
Check in this order
- Use only direct vent or indirect vent (combustion air from room) designs.
- Do not connect natural draft vent connectors into a positive pressure mechanical vent.
- Seal the vent system gastight.
- If there are more than 7 NPE water heaters, use 2 common vent systems or contact Navien.
Applies to: NCB700 with up to 7 NPE water heaters
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 Installation & Operation Manual, pp. 89-90. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.