Weil-McLain · Boiler troubleshooting

Zone valve zoning with direct connection piping (80/110/150 single boiler)

ECO Tec Series 3

What is going on

Use this layout only for zone valve systems that meet the direct connection criteria on page 53. If the system does not qualify, pipe it primary/secondary instead.

Check in this order

  1. Confirm the system meets the direct connection criteria on page 53; if not, use primary/secondary piping (pages 58 to 62).
  2. Install a by-pass pressure regulator (Taco 3196 or equivalent, Item 21) on zone valve systems, unless the circulator has dead-head protection.
  3. Provide a system expansion tank per the guidelines on page 54 or 57.
  4. Do not use a closed-type tank if the water heater has an automatic vent.
  5. For an indirect DHW tank, pipe it as a zone with zone valves so priority works and ghost flows are prevented.
  6. Wire zone valve end switches to the matching inputs. Use isolation relays for 3-wire end switches.
  7. Set TARGET MODULATION SENSOR to System Supply on page 123 when system sensors are installed.
  8. Check that the internal boiler circulator can supply the head and flow in Figure 58, page 48.

Applies to: ECO Tec 80/110/150 single boiler, zone valve direct connection (Figure 65)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 56. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.