Testing the fixed high limit (FHL)
What is going on
Checks that the FHL cuts out above its setting. Involves 120 VAC.
Check in this order
- Make sure connected low temperature (floor heating) systems are deactivated.
- Isolate attached DHW tanks and confirm the expansion tank will accept expansion.
- Power down the control with the power switch and disconnect the 120 VAC supply.
- Remove the two wires from the AHL, leaving the green ground wire connected.
- Fit the AHL jumper (from the accessory bag) between the two removed connectors.
- Reconnect 120 VAC and turn the control on.
- Create a continuous heat demand from the thermostat terminals so the boiler fires above the FHL setting.
- When the burner shuts down, let the boiler cool until the FHL resets, then press the centre of the FHL with a pen or small screwdriver.
- Disconnect 120 VAC, turn the power switch off, remove the AHL jumper and reinstall the two wires on the AHL.
- Reconnect 120 VAC, turn the control on, remove the thermostat call and confirm the burner shuts down.
- Return the AHL jumper to the accessory bag.
Applies to: Vitotronic 100 KW10B fixed high limit
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 KW10B installation, start-up and service instructions, p. 30. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.