Viessmann · Boiler troubleshooting

Testing the fixed high limit (FHL)

Vitotronic 100

What is going on

Checks that the FHL cuts out above its setting. Involves 120 VAC.

Check in this order

  1. Make sure connected low temperature (floor heating) systems are deactivated.
  2. Isolate attached DHW tanks and confirm the expansion tank will accept expansion.
  3. Power down the control with the power switch and disconnect the 120 VAC supply.
  4. Remove the two wires from the AHL, leaving the green ground wire connected.
  5. Fit the AHL jumper (from the accessory bag) between the two removed connectors.
  6. Reconnect 120 VAC and turn the control on.
  7. Create a continuous heat demand from the thermostat terminals so the boiler fires above the FHL setting.
  8. When the burner shuts down, let the boiler cool until the FHL resets, then press the centre of the FHL with a pen or small screwdriver.
  9. Disconnect 120 VAC, turn the power switch off, remove the AHL jumper and reinstall the two wires on the AHL.
  10. Reconnect 120 VAC, turn the control on, remove the thermostat call and confirm the burner shuts down.
  11. Return the AHL jumper to the accessory bag.

Applies to: Vitotronic 100 KW10B fixed high limit

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 KW10B installation, start-up and service instructions, p. 30. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.