Viessmann · Boiler troubleshooting
Burner motor power supply, 3 PH 208, 460 or 575 V
What is going on
For burners with three-phase supply at 208, 460 or 575 V. Fuse and wire sizing come from the burner manual.
Check in this order
- Disconnect power to the burner and the boiler control.
- Connect 3-phase power to terminals 21, 22, 23 and 24 on the DIN rail in the connection enclosure.
- Provide a fuseable disconnect according to local codes.
- Connect the supplied power cable to the motor terminals on the burner.
- Connect the cable plug to the socket on the DIN rail in the connection enclosure.
- During commissioning, check motor rotation and reverse BK1 and BK2 at the burner terminals if it turns the wrong way.
Applies to: VD2/VD2A/CT3 controls, 3 PH burners
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 GW2 installation and service instructions, p. 54. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.