Burner motor power supply, 3 PH 208, 460 or 575 V

Vitotronic 300

What is going on

For burners with three-phase supply at 208, 460 or 575 V. Fuse and wire sizing come from the burner manual.

Check in this order

  1. Disconnect power to the burner and the boiler control.
  2. Connect 3-phase power to terminals 21, 22, 23 and 24 on the DIN rail in the connection enclosure.
  3. Provide a fuseable disconnect according to local codes.
  4. Connect the supplied power cable to the motor terminals on the burner.
  5. Connect the cable plug to the socket on the DIN rail in the connection enclosure.
  6. During commissioning, check motor rotation and reverse BK1 and BK2 at the burner terminals if it turns the wrong way.

Applies to: VD2/VD2A/CT3 controls, 3 PH burners

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW2 installation and service instructions, p. 54. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.