Viessmann · Boiler troubleshooting
Checking the DHW flow limiter and filter (gas condensing combi)
What is going on
Inspect and clean or replace the DHW flow limiter and sieve on the combi boiler. Drain the DHW side first.
Likely causes
- Scaling on the flow limiter
- Damage to the flow limiter or sieve
Check in this order
- Remove the control unit and the burner, then drain the boiler on the DHW side.
- Remove the spring clip. On a B1KE-199, undo the G 3/4 inch union nut at the cold water inlet and the union nut on the upper side of the flow sensor, then pull the pipe out.
- Remove the DHW flow sensor.
- Check flow limiter A and filter sieve B. Replace them if scaled or damaged, then reinsert.
- Refit the DHW flow sensor with new gaskets in reverse order. Tighten the union nuts to 18 lb.ft (24 Nm).
- Check all water side connections for tightness.
Applies to: B1KE 120, B1KE 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 100-W B1HE/B1KE Combi Installation/Service, p. 57. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.