Weil-McLain · Boiler troubleshooting

Steam boiler operation verification

EGPEG

What is going on

Verify pilot and main burner flames and the vent damper before releasing the boiler.

Check in this order

  1. Check pilot flame blue, inner cone engulfing the thermocouple, thermocouple glowing cherry red.
  2. Correct overfired, underfired, lack of primary air, or incorrectly heated thermocouple.
  3. Check main burner flames yellow-orange streaks from dust are acceptable; correct large, small or yellow-tipped flames.
  4. Raise the room thermostat; the vent damper opens slowly, then the pilot lights and main burners ignite.
  5. Confirm the vent damper is fully open before main burners light.
  6. Lower the thermostat; main burners go out and the vent damper closes.
  7. Repeat several times, return thermostat to normal, set the heat anticipator per the wiring diagram.
  8. Check the vent system with a candle or match at the draft hood skirt once a month during heating season.

Applies to: EG / PEG steam boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: EG / PEG Series 7 boiler manual, p. 63-64. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.