Viessmann · Boiler troubleshooting

Check gas connections for leaks

Vitocrossal 200 CM2

What is going on

Check all gas fittings with a certified leak detection fluid. Do not let spray touch electrical parts.

Check in this order

  1. Install new gaskets in any gas fittings that were opened and tighten them.
  2. Open the gas shut-off valve.
  3. Check the gas valve inlet seals for tightness.
  4. Start the burner.
  5. Check the gas valve outlet seals and the fittings between the fan and boiler door and between the fan and venturi for tightness.

Applies to: Vitocrossal 200 CM2 186 to 311

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 21. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.