Shared vent removal test for old boiler
What is going on
When a SlimFit replaces a boiler on a common vent, the remaining appliances on that vent must be tested to confirm they still vent safely. The SlimFit cannot share the old common vent.
Likely causes
- Common vent now oversized for remaining appliances
- Blockage, leakage, corrosion, or wrong horizontal pitch in the old vent
Check in this order
- Inspect the old common vent for correct size, horizontal pitch, blockage, restriction, leakage, and corrosion.
- Seal any unused openings in the common vent system.
- Close building doors and windows and doors to other spaces. Turn on clothes dryers, non-vented appliances, and exhaust fans (range hood, bath) at full speed. Do not run a summer exhaust fan. Close fireplace dampers.
- Start the appliance being checked and let it run continuously.
- After 5 minutes of main burner operation, check the draft hood relief opening for spillage with a flame, candle, or smoke.
- Return doors, windows, fans, and dampers to their normal positions.
- Correct any common vent problem to meet NFGC or B149.1. Resize the common vent toward the minimum size from the code tables.
Applies to: Replacement of an existing boiler on a common vent
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit 1000-2000 Series 2 boiler manual, p. 26. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.