Shared vent removal test for old boiler

SlimFit Series 2

What is going on

When a SlimFit replaces a boiler on a common vent, the remaining appliances on that vent must be tested to confirm they still vent safely. The SlimFit cannot share the old common vent.

Likely causes

  • Common vent now oversized for remaining appliances
  • Blockage, leakage, corrosion, or wrong horizontal pitch in the old vent

Check in this order

  1. Inspect the old common vent for correct size, horizontal pitch, blockage, restriction, leakage, and corrosion.
  2. Seal any unused openings in the common vent system.
  3. Close building doors and windows and doors to other spaces. Turn on clothes dryers, non-vented appliances, and exhaust fans (range hood, bath) at full speed. Do not run a summer exhaust fan. Close fireplace dampers.
  4. Start the appliance being checked and let it run continuously.
  5. After 5 minutes of main burner operation, check the draft hood relief opening for spillage with a flame, candle, or smoke.
  6. Return doors, windows, fans, and dampers to their normal positions.
  7. Correct any common vent problem to meet NFGC or B149.1. Resize the common vent toward the minimum size from the code tables.

Applies to: Replacement of an existing boiler on a common vent

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit 1000-2000 Series 2 boiler manual, p. 26. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.