What is going on
Sizes are based on the total input of all oil-fired appliances in the space. Louvers and screens reduce free area, so allow for them.
Check in this order
- Unconfined space provide 1 sq in per 5,000 Btu/h (4.5 sq cm per kWh) of total input, or use outdoor or freely communicating air.
- Confined space using indoor air two permanent openings, one near the top and one near the bottom, each 1 sq in per 1,000 Btu/h (19.5 sq cm per kWh).
- Confined space using outdoor air, vertical duct: 1 sq in per 4,000 Btu/h (5.5 sq cm per kWh) per duct.
- Confined space using outdoor air, horizontal duct under 50 ft (15 m) equivalent length: 1 sq in per 2,000 Btu/h (11 sq cm per kWh).
- Confined space using outdoor air, direct openings to outside: 1 sq in per 4,000 Btu/h (5.5 sq cm per kWh).
- Allow for louver free area wood louvers 20 to 25 percent, metal louvers and grilles 60 to 75 percent, unless the manufacturer states the free area.
- Use screens no smaller than 1/4 in (6 mm) mesh and keep them accessible for cleaning.
Applies to: VR1 22 to 33, 91 to 140
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 100 installation and service manual, p. 10. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.