Viessmann · Boiler troubleshooting

Size combustion air openings

Vitorond 100 VR1

What is going on

Sizes are based on the total input of all oil-fired appliances in the space. Louvers and screens reduce free area, so allow for them.

Check in this order

  1. Unconfined space provide 1 sq in per 5,000 Btu/h (4.5 sq cm per kWh) of total input, or use outdoor or freely communicating air.
  2. Confined space using indoor air two permanent openings, one near the top and one near the bottom, each 1 sq in per 1,000 Btu/h (19.5 sq cm per kWh).
  3. Confined space using outdoor air, vertical duct: 1 sq in per 4,000 Btu/h (5.5 sq cm per kWh) per duct.
  4. Confined space using outdoor air, horizontal duct under 50 ft (15 m) equivalent length: 1 sq in per 2,000 Btu/h (11 sq cm per kWh).
  5. Confined space using outdoor air, direct openings to outside: 1 sq in per 4,000 Btu/h (5.5 sq cm per kWh).
  6. Allow for louver free area wood louvers 20 to 25 percent, metal louvers and grilles 60 to 75 percent, unless the manufacturer states the free area.
  7. Use screens no smaller than 1/4 in (6 mm) mesh and keep them accessible for cleaning.

Applies to: VR1 22 to 33, 91 to 140

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 100 installation and service manual, p. 10. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.