Viessmann · Boiler troubleshooting

LON communication interrupted

Vitotronic 100

What is going on

The control unit shows when LON communication between control units is interrupted. Terminal resistors are required on the first and last control unit.

Likely causes

  • Broken or missing connecting cable between control units.
  • Terminal resistor missing on the first or last control unit.

Check in this order

  1. Check the connecting cable between the control units.
  2. Confirm a terminal resistor is fitted on the first and last control unit.
  3. Confirm the LON module is seated in the control unit.

Applies to: Vitotronic 100 GC1 with LON communication module 7172 173

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 installation and service instructions, p. 111. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.