Closure switch (flow switch or CAD) interlock wiring
What is going on
Optional proof-of-closure interlock. Remove the jumper on terminal strip P11 to use a flow switch or combustion air damper (CAD) interlock. No control settings are needed for a flow switch. For a CAD, the recommended setup is to assign INPUT 3 as an AUX PUMP/OUTPUT, set the output to ANY BURNER DEMAND, and wire OUTPUT 3 (120 VAC) to the damper motor. The control gives the switch 4 minutes to close. A lockout occurs if it stays open or opens during firing, and it clears when the switch closes again.
Likely causes
- Closure switch stays open after 4 minutes
- Closure switch opens while the burner is firing
Check in this order
- Remove the P11 jumper only when a flow switch or CAD interlock is used.
- Use devices with electrically isolated contacts, because the P7 jumper circuit carries 5 VDC.
- For CAD wiring, assign INPUT 3 as AUX PUMP/OUTPUT and set the output mode to ANY BURNER DEMAND.
- Use an isolation relay if the damper motor needs a different voltage or draws more than 2.2 A on 120 VAC.
- If the lockout persists, check the damper or flow switch closes and conducts when a call for heat starts.
Applies to: SF1000L/R, SF1500L/R, SF2000L/R
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 Boiler Manual 550-100-561/1225, p. 56. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.