Direct vent: down-turned air inlet elbow

Ultra Series 4

What is going on

The air inlet is a direct vent connection, so it is not treated as a forced air intake for spacing from other vents. Its location must keep flow clear of plants and exhaust from other appliances.

Check in this order

  1. Use the left-side configuration unless the terminations would fail the minimum clearance to grade or snow line.
  2. Use the right-side configuration when the terminations must be raised to meet the grade or snow line clearance.
  3. Place the air inlet at least 12 in below and 12 in horizontally from any appliance or building vent outlet.
  4. Keep the air inlet clear of obstructions and plants that could block air flow.
  5. If the air pipe runs up the building side, brace it no further than 24 in apart and keep all clearances and lengths.

Applies to: Direct vent vertical vent / sidewall air, air inlet elbow

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 boiler manual, p. 80. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.