Direct vent: down-turned air inlet elbow
What is going on
The air inlet is a direct vent connection, so it is not treated as a forced air intake for spacing from other vents. Its location must keep flow clear of plants and exhaust from other appliances.
Check in this order
- Use the left-side configuration unless the terminations would fail the minimum clearance to grade or snow line.
- Use the right-side configuration when the terminations must be raised to meet the grade or snow line clearance.
- Place the air inlet at least 12 in below and 12 in horizontally from any appliance or building vent outlet.
- Keep the air inlet clear of obstructions and plants that could block air flow.
- If the air pipe runs up the building side, brace it no further than 24 in apart and keep all clearances and lengths.
Applies to: Direct vent vertical vent / sidewall air, air inlet elbow
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 boiler manual, p. 80. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.