Weil-McLain · Boiler troubleshooting
Burner access, cleaning and replacement
What is going on
Remove the mixing tube assembly to reach the burner.
Check in this order
- Turn off all power to the boiler.
- Disconnect the two wire harnesses to the blower.
- Remove the three nuts that hold the mixing tube to the right-end heat exchanger section, using a 13 mm socket.
- Pull the mixing tube, blower, venturi and gas train to the right to clear the stud, then pull forward and support them.
- If needed, disconnect the ignitor ground wire and the harnesses to the gas valve and gas pressure switches.
- Remove the burner gasket and burner.
- Clean the burner ports inside and outside with a vacuum or compressed air. Use a soft brush if needed to loosen particles.
- Use compressed air only outdoors and wear eye protection.
- Insert the burner first. Place a hand in the burner throat and tilt the back up until the flange meets the heat exchanger, so it does not rub the burner support stubs.
- Align the burner flange notch with the notch in the casting above the opening.
- Check the burner gasket. Replace it if it is not in good condition.
- Place the gasket over the three studs. The studs are unevenly spaced to set the gasket and mixing tube correctly.
- Position the mixing tube over the studs. Install the three nuts and tighten to 12 N-m (106 in-lb, 8.8 ft-lb).
- Reconnect all wiring, then retest and confirm the flame is acceptable.
Applies to: SlimFit 550 and 750 Series 3
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit series3 commercial gas-fired water boiler boiler manual, p. 94. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.