Viessmann · Boiler troubleshooting

Boiler in heating/cooling application with chiller

Vitodens 200-W

What is going on

When the boiler is used with a refrigeration system, the chilled medium must be piped in parallel with the boiler. Valves must stop chilled water from entering the boiler. Coils in air handlers exposed to cooled air need flow control or another automatic means to stop gravity circulation of boiler water during cooling.

Check in this order

  1. Pipe the chiller in parallel with the boiler using valves that keep chilled medium out of the boiler.
  2. Fit a spring-loaded flow check valve and a circulation pump as shown in the layout.
  3. Run the circulating pump from its own on/off switch, not from the boiler pump aquastat.
  4. Label the changeover valves v1 and v2.
  5. Check the chiller manufacturer's installation instructions for any extra requirements.

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 200-W B2HA 80 to 100, 285 to 352 installation manual, p. 44. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.