Viessmann · Boiler troubleshooting
Wire zone controller dry contact to R-Stat input (no outdoor reset)
What is going on
Boiler runs from zone controller heat demand, not outdoor reset. The Como OT cannot be used in this setup. When a zone thermostat calls, its dry contact closes the R-Stat input, which starts the space heating pump output and calls the zone controller to open the zone. Each zone thermostat still controls its own zone valve or pump.
Check in this order
- Disconnect power to the Versatronik 10.WB1 and the zone control.
- Remove the ZC/ZR jumper from the zone controller.
- Connect the L output of the Versatronik space heating pump output to the ZC terminal of the zone controller.
- Connect the potential-free (dry contact) output of the zone controller to the Versatronik R-Stat input terminals.
- Power both devices and test operation.
Applies to: Versatronik 10.WB1 without outdoor reset
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 10.WB1 installation and operating manual, p. 17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.