Install direct vent sidewall air and vent terminations

SlimFit Series 2

What is going on

Sidewall direct vent uses corrosion-resistant stop plates sized just over the pipe diameter, sourced only from the vent pipe manufacturer. Vent and air pipe shoulders must rest against the outer stop plates so the pipes cannot be pushed inward. Exposed pipe up to 4 ft needs bracing every 24 in. Longer exposed runs need an insulated enclosure with terminations exiting through it. Seal all exterior openings with exterior caulk and fit bird screens to both terminal elbows.

Check in this order

  1. Cut the vent pipe hole. For combustible walls, make it at least 3/8 in larger than the vent pipe; for noncombustible walls, follow the vent maker's sizing.
  2. Install a corrosion-resistant metal thimble in the vent hole and follow local code for wall penetrations.
  3. Fit the outer stop plates (hole just larger than pipe) from the vent maker only.
  4. Insert the last vent and air lengths from outside until the female shoulders seat against the stop plates.
  5. Attach the outward-facing 90-degree vent elbow and the down-turned 90-degree air elbow.
  6. Brace the exposed pipe every 24 in or closer; leave no more than 4 ft exposed without an enclosure.
  7. Install bird screens in both terminal elbows and seal exterior openings with exterior caulk.
  8. For multiple boiler terminations, follow the spacing shown in the manual's multiple termination figure.

Applies to: SlimFit SF1000L/R, SF1500L/R, SF2000L/R direct vent sidewall installations

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SlimFit Series 2 boiler manual, p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.