Select and calculate antifreeze amount
What is going on
Use only freeze-prevention fluids approved by WM Technologies for SVF boilers. Sentinel X500 is approved. Never use automotive or standard glycol.
Check in this order
- Determine the freezing temperature needed for the lowest likely system water temperature.
- Find the antifreeze percentage by volume for that temperature from the manufacturer's data.
- Calculate total system water volume, including piping, components, expansion tank and boiler. Boiler water content is in Table 27 (p. 142).
- Multiply total volume by the antifreeze percentage to get gallons of antifreeze.
- Check that flow rate and temperature rise still meet Table 5 (p. 21).
Applies to: SVF 500/600 Series 1
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SVF 500/600 Series 1 boiler manual, p. 93. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.