Viessmann · Boiler troubleshooting
Check room temperature sensor (Part No. 7133 379)
What is going on
Measure the sensor resistance at its terminals and compare it with the current room temperature. Scan the current room temperature on the control first (see page 74).
Likely causes
- Room temperature reading seems wrong
- Remote control cannot be placed where it measures room temperature correctly
Check in this order
- Disconnect the wires at the sensor terminals.
- Measure the resistance of the sensor between terminals 9 and 13b.
- Compare the value with the current room temperature using the resistance table.
- If the value differs significantly, check the installation and replace the sensor if necessary.
Applies to: Room temperature sensor, Part No. 7133 379
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300, Model GW2 installation and service instructions, p. 112. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.