Viessmann · Boiler troubleshooting

Check outside temperature sensor

Vitocrossal 200 CI2

What is going on

Resistance check of the outside temperature sensor and its lead. The lead is 2-wire, up to 115 ft (35 m), 16 AWG (1.5 mm2).

Likely causes

  • Faulty outside temperature sensor
  • Faulty or damaged lead

Check in this order

  1. Check the lead and plug of the outside temperature sensor.
  2. Disconnect wires 1 and 2 from the terminal on the wiring panel.
  3. Measure the sensor resistance and compare it with the value for the current temperature on the curve.
  4. If the result deviates by more than 10%, disconnect the wires from the sensor and repeat the test at the sensor.
  5. Check the on-site cable.
  6. Replace the lead or the outside temperature sensor as needed.

Applies to: Vitocrossal 200 CI2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 Service Instructions, p. 78. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.