Check outside temperature sensor
What is going on
Resistance check of the outside temperature sensor and its lead. The lead is 2-wire, up to 115 ft (35 m), 16 AWG (1.5 mm2).
Likely causes
- Faulty outside temperature sensor
- Faulty or damaged lead
Check in this order
- Check the lead and plug of the outside temperature sensor.
- Disconnect wires 1 and 2 from the terminal on the wiring panel.
- Measure the sensor resistance and compare it with the value for the current temperature on the curve.
- If the result deviates by more than 10%, disconnect the wires from the sensor and repeat the test at the sensor.
- Check the on-site cable.
- Replace the lead or the outside temperature sensor as needed.
Applies to: Vitocrossal 200 CI2
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 Service Instructions, p. 78. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.