Weil-McLain · Boiler troubleshooting
Install the relief valve and discharge line
What is going on
The relief valve mounts in a 3/4 in. street elbow on the boiler supply tee. The discharge line must be installed to protect people and property from hot water or steam discharge.
Check in this order
- Install the relief valve in the 3/4 in. street elbow piped from the boiler supply tee. Pipe it only as shown in the manual.
- Connect the discharge piping to a safe disposal point. Keep it as short as possible and the same size as the valve outlet along its whole length.
- Pitch the discharge line downward from the valve. End it at least 6 in. above a floor drain where discharge is visible.
- End the discharge line plain, not threaded, using material rated for 375 °F or higher.
- Do not route the discharge where freezing can occur. Do not place a shutoff valve between the relief valve and boiler or in the discharge line. Do not plug or obstruct the discharge line.
- After filling and pressurizing, lift the lever to test the valve. Confirm it discharges freely. Replace the valve if it does not operate correctly.
Applies to: All Ultra Series 4 models
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 boiler manual, p. 9. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.