Hydrostatic pressure test of the boiler before startup
What is going on
The boiler must be leak tested before piping or power is connected. Test at no more than 1.5 times the maximum operating pressure. Do not exceed the listed pressure or temperature limits, or the warranty is void.
Likely causes
- Pressure above the listed limits can damage the boiler
- Leaks at pipe joints, safety devices or the boiler base
Check in this order
- Install safety devices, then fit a temporary cap on the 3/4 in. nipple used for the relief valve.
- Cap the supply and return connections.
- Connect a 1/2 in. garden hose to the boiler drain valve and fill slowly until the gauge reads 68 psi (4.65 bar).
- Hold pressure for 15 minutes and stay with the boiler during the test.
- Check all pipe joints, safety devices (safety header if fitted) and the boiler base with a flashlight for leaks.
- Open the drain valve slowly to release pressure, then remove the caps.
- Install the pressure relief valve in place of the 3/4 in. cap before startup.
Applies to: Vitorond 100 VR1 40 to 63 and 161 to 245 oil-fired boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 100 VR1 installation and service manual, p. 25. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.