What is going on

The boiler has a built-in condensate trap, so no external trap is needed when using flexible discharge tubing. Drain must be sloped and must not siphon the boiler.

Likely causes

  • Condensate outlet below the drain point, which needs a pump
  • Discharge tubing pushed up into the housing as shipped

Check in this order

  1. Use 1 in. (25 mm) field-supplied discharge tubing.
  2. Use CPVC or PVC approved by the listed codes. Drain pipe and fittings must meet ANSI, ASTM D1785 or D2846. Cement and primer must meet ASTM D2564 or F493. In Canada use CSA or ULC listed schedule 40 CPVC or PVC.
  3. If the condensate outlet is lower than the drain, install a condensate pump approved for condensing boilers. Choose a pump with an overflow switch.
  4. Terminate the drain into an open or vented drain as close to the boiler as possible to prevent siphoning.
  5. Install the drain pipe with a suitable gradient and pull the hose out of the boiler so no unnecessary bends form inside.
  6. Pull the flexible discharge tubing down so condensate can drain.
  7. Check that siphon connection A is tight.
  8. Keep pipe ventilation between the siphon trap and any neutralization unit.
  9. Do not connect drains from other appliances, such as a water softener backwash, into the condensate line.
  10. Discharge condensate to the drain system directly or through a neutralization unit (accessory) if required.

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 222-F, B2TB installation instructions, p. 22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.