Viessmann · Boiler troubleshooting

Check static gas pressure

Vitocrossal 200 CI2

What is going on

Confirm the static gas pressure at the inlet test connector. Maximum is 14 in w.c.

Check in this order

  1. Close the gas shut-off valve.
  2. Loosen the screw in test connector A without removing it.
  3. Connect the pressure gauge to test connector A.
  4. Open the gas shut-off valve.
  5. Check that static pressure is no more than 14 in w.c.
  6. Record the reading on the maintenance record (page 95).
  7. Check all connections for gas tightness with soap and water.

Applies to: Vitocrossal 200 CI2 399 to 2000 MBH

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 service instructions, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.