Viessmann · Boiler troubleshooting
Condensate drain installation
What is going on
Route condensate through a P-trap or siphon so flue gas cannot enter the room. The boiler has a field-installed condensate trap, so no external trap is needed when the field drain connects to the P-trap. The external connection is a barb fitting, about 19 mm (inch size is garbled in the text). Use 1 in. diameter discharge tubing. The drain must end in an open or vented drain close to the boiler and must be visible for inspection. Do not tie in drains from other appliances such as a water softener backwash.
Check in this order
- Connect the condensate drain to the boiler barb and fit a P-trap or siphon.
- Run 1 in. diameter CPVC, PVC or other approved drain pipe with a continuous fall toward the drain.
- Terminate the drain in an open or vented drain as close to the boiler as possible.
- If the boiler sits at ground level, keep the condensing drain max. 2 in. (50 mm) above ground.
- If the condensate outlet is below the drain, install an approved condensing-boiler pump with an overflow switch.
- Vent the pipe between the siphon trap and the neutralization unit if one is used.
- Use drain pipe and cement that meet ASTM D1785 or D2846 and ASTM D2564 or F493; in Canada use CSA or ULC listed schedule 40 CPVC or PVC.
Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocrossal 300 CA3B Dual Fuel installation manual, p. 40. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.