Viessmann · Boiler troubleshooting
Checking solar and multifunction relay status
What is going on
Solar and multifunction values only show for functions that are implemented and activated. Collector pump status is only configured when two collectors in east-west alignment charge one or more tanks, or when several tanks are charged by the solar system with switch-over valves.
Check in this order
- Read T-MF1 to T-MF4 for the sensor assigned to each multifunction relay.
- Read MF1 to MF4 for the on/off state of each multifunction relay.
- Read T-Solar 1 and T-Solar 2 for collector temperatures.
- Read Sol pump 1, 2 or 3 for collector pump status, only where configured.
- Read Charge ST HW, Charge ST BU or Charge ST 3 for storage charging pump or switch-over valve status.
- Read Charge DHW2 or Charge BU2 for transfer pump status on cascade storage tanks.
Applies to: Solar and multifunction relay setups on the Versatronik 200
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 200 installation and operating manual, p. 100. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.