Viessmann · Boiler troubleshooting

LON network wiring

Vitocontrol-S VD2/CT3/CM2Vitotronic 100

What is going on

Viessmann LON uses line BUS topology with end-of-line resistors at both ends. The two wires and shielding are always required; wires are interchangeable. Follow FTT-10A cabling rules.

Check in this order

  1. Use Viessmann LON cable part 7143 495 between control units or Vitocom.
  2. Fit end-of-line resistor part 7143 497 at both ends of the line.
  3. Use the LON extension jack part 7143 496 for coupling; max 3 cables between two devices.
  4. For on-site cable extensions up to 900 m / 3000 ft, use junction boxes; up to 99 participants.

Applies to: LON communication

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitocontrol-S VD2/CT3/CM2 installation manual, p. 86-87. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.