Viessmann · Boiler troubleshooting

Replace air pressure switch (LDW1 / LDW2)

Vitocrossal 300 CA3B Dual Fuel

What is going on

LDW1 is the fan air pressure switch and LDW2 is the combustion chamber air pressure switch. Set the new switch to the same value as the old one.

Check in this order

  1. Undo the 2 mounting screws (torque 9 lb.in / 1 Nm) and remove the display and programming unit from the burner control unit.
  2. Pull connector aCA (LDW1) and connector aCAA (LDW2) from the plug-in strip on the burner control unit.
  3. Pull the compensation hose from the connector.
  4. Undo the mounting screw(s) on the air pressure switch and remove the cover (torque 9 lb.in / 1 Nm).
  5. Undo the base mounting screws and remove the base.
  6. Install the new air pressure switch in reverse order and observe torque settings.
  7. Attach the connection hose to the corresponding connector.
  8. Set the new switch to exactly the same value as the replaced switch.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 Dual Fuel Service Instructions, p. 63. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.