Viessmann · Boiler troubleshooting
Replace air pressure switch and compensation hose (LDW1/LDW2)
What is going on
LDW1 is the fan air pressure switch and LDW2 is the combustion chamber air pressure switch. The new switch must be set to the same value as the one it replaces.
Check in this order
- Undo the 2 mounting screws (torque 9 lb.in / 1 Nm) and remove the display and programming unit from the burner control.
- Pull connector aCA (LDW1) and connector aCAA (LDW2) from the plug-in strip.
- Pull the compensation hose from the connector.
- Remove the air pressure switch cover (torque 9 lb.in / 1 Nm on reinstall).
- Undo the base mounting screws and remove the base.
- Install the new switch in reverse order and observe torque settings.
- Attach the hose to the matching connector: '-' for LDW1, '+' for LDW2.
- Set the new switch to the same value as the replaced switch.
- If replacing the hose, cut the replacement to the length in the hose table.
Applies to: CA3B Series 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 service instructions, p. 62. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.