Checking the boiler out sensor
What is going on
Check the boiler out resistance-type sensor against Table 16 and confirm the control reads it correctly.
Check in this order
- Turn off all power to the boiler before servicing.
- Measure sensor resistance with an ohmmeter in water at known temperatures: 32°F (freezing), room temperature, and 212°F (sea-level boiling). Insert the sensor in the water for the freezing and boiling points.
- Compare each reading with the expected range in Table 16.
- To check the control, temporarily connect a resistance decade box in place of the sensor and confirm the control display shows the matching temperature.
- Do not leave jumpers or bypasses installed after testing.
Applies to: EG and PEG Series 7 water boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: EG / PEG Series 7 Boiler Manual, p. 73. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.