Weil-McLain · Boiler troubleshooting

Checking the boiler out sensor

EG / PEG Series 7

What is going on

Check the boiler out resistance-type sensor against Table 16 and confirm the control reads it correctly.

Check in this order

  1. Turn off all power to the boiler before servicing.
  2. Measure sensor resistance with an ohmmeter in water at known temperatures: 32°F (freezing), room temperature, and 212°F (sea-level boiling). Insert the sensor in the water for the freezing and boiling points.
  3. Compare each reading with the expected range in Table 16.
  4. To check the control, temporarily connect a resistance decade box in place of the sensor and confirm the control display shows the matching temperature.
  5. Do not leave jumpers or bypasses installed after testing.

Applies to: EG and PEG Series 7 water boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: EG / PEG Series 7 Boiler Manual, p. 73. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.