Viessmann · Boiler troubleshooting
Return valve protection with mixing valve (Circuit Diagram 7)
What is going on
When return temperature falls below the minimum, the 3-port mixing valve on the boilers closes proportionally via sensor T1 to protect the boiler.
Likely causes
- Return temperature below required minimum
Check in this order
- Verify sensor T1 is connected at plug aJA and coding 4A is set to 4A: 1.
- Verify continuous return temperature control is set (0C: 1).
- Verify boiler circuit pump is connected at plug sL (4d: 2).
Applies to: Circuit Diagram 7, old systems or systems with no facility for adjusting downstream heating circuits
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 100 GC1 installation and service instructions, p. 20. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.