Rinnai · Boiler troubleshooting

Program cascade communication and secondary IDs

I-Series Plus

What is going on

Sets up the Primary boiler and assigns an ID to each secondary water heater in the cascade.

Check in this order

  1. Select the I-Series Combi Boiler to be the Primary unit.
  2. Set that boiler's parameter 71 to b (Primary).
  3. Set parameter 72 to the number of units to hold in standby.
  4. On each secondary water heater, press the On/Off button on its controller to set the Secondary ID.
  5. Wait for the display to change from - - - to the new ID number to confirm the ID was set.

Applies to: I-Series Plus Combi Boiler with CX/CXP cascade

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 106. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.