Weil-McLain · Boiler troubleshooting

Set up 0-10 Vdc remote modulation

SVF 500/600 Series 1

What is going on

Used when the boiler's firing rate is driven by an external 0-10 Vdc signal instead of a thermostat contact. Input 2 is replaced by the modulation input.

Check in this order

  1. Wire the 0-10 Vdc positive to J16 terminal 6 and the common to J16 terminal 5.
  2. Do not wire any device to Input 2.
  3. If indirect DHW is also used, connect the DHW aquastat to Input 3 or Input 4 and assign it to Priority 2.
  4. Assign Input 2 to Priority 3 and accept the Wizard defaults for Input 2.
  5. After the Wizard, go to SYSTEM SETTINGS, then Input Usage, and change the Input 2 SOURCE from TT1 to 0-10V.
  6. Verify the priority settings suit the application.

Applies to: SVF 500/600 Series 1 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SVF 500/600 Series 1 boiler manual 550-100-273/1224, p. 77. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.