Viessmann · Boiler troubleshooting

Boiler control power supply, 120 VAC 1 PH

Vitotronic 300

What is going on

Main supply to the control. Overcurrent protection and disconnect must follow local codes. The control must be grounded.

Check in this order

  1. Ensure the main supply has overcurrent protection rated at no more than 15 A and a 2-pole disconnect.
  2. Connect the supply to terminals 11, N and G on the DIN rail in the connection enclosure.
  3. Make sure L, N and G are not swapped.
  4. Ground the control.

Applies to: VD2/VD2A/CT3 controls, 120 VAC 1 PH supply

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW2 installation and service instructions, p. 55. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.