Boiler control power supply, 120 VAC 1 PH
What is going on
Main supply to the control. Overcurrent protection and disconnect must follow local codes. The control must be grounded.
Check in this order
- Ensure the main supply has overcurrent protection rated at no more than 15 A and a 2-pole disconnect.
- Connect the supply to terminals 11, N and G on the DIN rail in the connection enclosure.
- Make sure L, N and G are not swapped.
- Ground the control.
Applies to: VD2/VD2A/CT3 controls, 120 VAC 1 PH supply
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 GW2 installation and service instructions, p. 55. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.