Blower not at stand-still before a call for heat
What is going on
On a call for heat the blower must read below 300 rpm within 51 seconds. Otherwise the start-up sequence cannot begin.
Check in this order
- Check the blower speed reading at start-up.
- Confirm the blower is below 300 rpm within 51 seconds.
Applies to: Vitodens 200-W B2HA 45 and 60
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 88. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.