Weil-McLain · Boiler troubleshooting

Check gas supply pressure at the gas valve

SlimFit Series 2

What is going on

Measure inlet pressure at the 1/8 in Port 2 on the gas valve with a manometer or gauge. Confirm minimum gas pressure while gas is flowing and the boiler is at high fire during startup. The supply must stay below the high gas pressure switch setting when static or with the boiler on.

Likely causes

  • Undersized supply piping
  • Supply regulator set too high or too low

Check in this order

  1. Connect a manometer or gauge to the 1/8 in Port 2 on the gas valve.
  2. Verify all other gas appliances are running.
  3. During startup, confirm the boiler at high fire reads at least 3 in w.c. with gas flowing.
  4. Set the supply regulator so the supply stays well below 14 in w.c. and won't trip the high gas pressure switch.

Applies to: SlimFit Series 2 gas valve inlet pressure check

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SlimFit Series 2 boiler manual, p. 45. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.