Viessmann · Boiler troubleshooting
Main power, pump and room thermostat connections
What is going on
Main supply is 120V, 60Hz, single phase. Pump, DHW and room thermostat terminals are on the power pump module. The room thermostat anticipator is set to 0.2A. The wiring diagram on the inside of the front cover supersedes the manual wiring information. Wiring diagram is also on page 91.
Check in this order
- Remove the short factory test leads from terminals L, N and Ground before connecting the main supply.
- Provide a main power disconnect or service switch per local code.
- Connect the heating circuit pump, or the boiler pump for a low-loss header or CombiPLUS pump.
- Connect the room thermostat with 0.2A anticipator setting.
- If a DHW tank controller or external heat demand is used, connect it (not used with the CombiPLUS kit).
- Install a pressure-activated bypass when using system layout 1 (see page 38).
Applies to: Vitodens 100-W WB1B field wiring
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 100-W WB1B installation and service manual, p. 51. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.